Samsung EHS Fault Codes

Complete reference of Samsung EHS heat pump error codes with causes and solutions. Search by code number or keyword to quickly diagnose issues.

Most Common EHS Errors

E911E912

Flow-Related Errors

The most reported errors on forums. E911 indicates low or no flow when the system expects it; E912 indicates flow when there should be none.

Common causes

  • Flow switch failures or sensitivity issues
  • Air trapped in the system
  • Dirty or clogged filters
  • Zone valves not opening fast enough
  • Insufficient flow rate (need >20 L/min)
  • Stuck relay, faulty PCB, or thermosiphon effect (E912)

Solutions

  • Install an inline flow meter to verify actual flow rate
  • Add an automatic bypass valve
  • Ensure flow rate exceeds 20 L/min
  • Bleed all air from the system thoroughly
  • Clean or replace filters and strainers
  • Check that zone valves open before the compressor starts
  • For E912: add non-return valve, inspect relay/PCB
E919

Legionella Cycle Failure

The built-in legionella disinfection cycle (runs at 3am Tuesday by default) failed to reach 60°C within 8 hours.

Common causes

  • Incorrectly positioned tank sensor (not deep enough into pocket)
  • Immersion heater thermostat set below 60°C
  • Immersion heater element failed
  • Sensor positioned below the immersion element

Solutions

  • Check sensor position — must be 100mm into tank pocket, above the immersion element
  • Set immersion thermostat above 60°C
  • Test immersion heater element for continuity
  • Consider disabling Samsung's built-in cycle (FSV 3041 = 0) and using a weekly timer instead
E101

Indoor/Outdoor Communication Error

The indoor unit cannot receive data from the outdoor unit. Usually wiring-related, this is one of the first errors to appear after installation.

Common causes

  • Disconnected or damaged communication cables
  • Wrong cable type (must use 16/2 stranded shielded cable)
  • Cable grounded at both ends (should only be grounded at outdoor unit)
  • Blown PCB from electrical fault
  • Electromagnetic interference from nearby power cables

Solutions

  • Inspect all cables between indoor and outdoor units
  • Verify correct cable type: 16/2 stranded shielded
  • Ensure cable shield is grounded at the outdoor unit only
  • Check for visible damage or corrosion on connectors
  • Route communication cables away from power cables
  • Replace PCB if damaged

Full Fault Code Reference

Communication

CodeDescription
E101Indoor can't receive data from outdoor
Causes:Disconnected/damaged cables; Blown PCB
Solutions:Check cables; Inspect for damage; Replace PCB
E102Outdoor unit cannot communicate
Causes:Similar to E101 — cable or PCB fault
Solutions:Check wiring between units
E108Repeated communication address issue
Causes:Duplicate indoor unit addresses
Solutions:Reconfigure unit addresses
E185Cross-wiring: comm/power cable swapped
Causes:Installation error
Solutions:Correct cable wiring
E186SPi connection error
Causes:SPi module fault
Solutions:Check SPi connections
E201Indoor unit address / comm failure
Causes:Address DIP switch misconfiguration
Solutions:Verify addresses; Check wiring
E202Indoor/outdoor comm failure
Causes:Cable fault; Interference
Solutions:Check cables
E203Main/sub outdoor PCB comm error
Causes:PCB fault
Solutions:Check outdoor PCB connections
E205All PBA within outdoor unit comm error
Causes:Multiple board failures
Solutions:Professional service required
E210Outdoor unit/MCU comm error
Causes:Wiring or MCU fault
Solutions:Check MCU wiring
E601Remote controller/indoor unit comm error
Causes:Loose thermostat wiring
Solutions:Check thermostat wiring; Reset by powering off for 5 minutes
E602Master/slave remote controller comm error
Causes:Inter-controller wiring fault
Solutions:Check interconnect wiring
E6037-day scheduler/remote controller comm error
Causes:Scheduler connection fault
Solutions:Check scheduler wiring
E604Remote/DVM Hydro tracking error
Causes:Configuration or wiring fault
Solutions:Reconfigure tracking

Indoor Sensors

CodeDescription
E121Room temperature sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E122Evaporator inlet pipe temp sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E123Evaporator outlet sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E128Evaporator inlet sensor detached
Causes:Sensor not secured
Solutions:Reattach sensor
E129Evaporator outlet sensor detached
Causes:Sensor not secured
Solutions:Reattach sensor
E130Both evaporator sensors detached
Causes:Both sensors loose
Solutions:Reattach both sensors
E131Auxiliary electric heater sensor 1 error
Causes:Sensor failure
Solutions:Replace sensor
E132Auxiliary electric heater sensor 2 error
Causes:Sensor failure
Solutions:Replace sensor
E133Auxiliary electric heater sensor 3 error
Causes:Sensor failure
Solutions:Replace sensor
E134Shutter sensor error
Causes:Sensor failure
Solutions:Replace sensor
E135Fan sensor / RPM feedback error
Causes:Fan sensor failure
Solutions:Check fan sensor
E140MCU temperature sensor (open/short)
Causes:MCU sensor failure
Solutions:Replace sensor

Indoor Operational

CodeDescription
E151EEV failure to open
Causes:Valve stuck; Electrical fault
Solutions:Check EEV wiring; Replace valve
E152EEV failure to close
Causes:Valve stuck
Solutions:Check EEV; Replace valve
E153Float switch detection
Causes:Condensate overflow
Solutions:Check drain; Clean float switch
E154Indoor fan motor not rotating
Causes:Failed motor; Obstruction
Solutions:Check fan blade; Replace motor
E161Mixed heating/cooling operation
Causes:Control logic fault
Solutions:Reset unit; Check configuration
E162EEPROM error
Causes:Corrupted memory
Solutions:Replace indoor PCB
E163Option code setting error
Causes:Incorrect DIP switch settings
Solutions:Correct DIP switch settings
E165Electric heater discharge temp protection
Causes:Overheating
Solutions:Check heater and airflow
E166Missing fan during heater operation
Causes:Fan not running during heater use
Solutions:Check fan operation
E198Indoor thermal fuse opened
Causes:Overheating protection triggered
Solutions:Check cause of overheating; Replace fuse

Outdoor Sensors

CodeDescription
E221Outside temperature sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E226Outside temperature sensor disconnected
Causes:Sensor detached
Solutions:Reattach or replace sensor
E231Condenser outlet main temp sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E236Condenser outlet 1 sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E251Compressor discharge temp sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E271Sump temperature sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E291High pressure sensor (open/short) / refrigerant leak
Causes:Sensor fault; Refrigerant leak
Solutions:Check sensor; Check for leaks
E296Low pressure sensor (open/short) / refrigerant leak
Causes:Sensor fault; Refrigerant leak
Solutions:Check sensor; Check for leaks
E301High pressure sensor disconnected
Causes:Sensor detached
Solutions:Reattach sensor
E306Low pressure sensor disconnected
Causes:Sensor detached
Solutions:Reattach sensor
E308Suction temperature sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E311Liquid pipe sensor (open/short)
Causes:Sensor failure
Solutions:Replace sensor
E474Inverter heatsink temp sensor error
Causes:Sensor failure
Solutions:Replace sensor

Compressor/Inverter

CodeDescription
E461Inverter compressor startup failure
Causes:Mechanical or electrical fault
Solutions:Professional service required
E462Total current error / compressor stop
Causes:Overcurrent
Solutions:Check power supply
E464IPM over-current error
Causes:Short circuit; Compressor failure
Solutions:Professional service required
E465Compressor V-limit/I-limit error
Causes:Voltage or current limits exceeded
Solutions:Check power supply
E466DC-Link over/low voltage
Causes:Power fluctuation
Solutions:Check mains supply
E467Compressor wire missing/unconnected
Causes:Loose wiring
Solutions:Check compressor cables
E468Inverter output current sensor error
Causes:Current sensor failure
Solutions:Replace PBA
E469Inverter DC voltage sensor error
Causes:Voltage sensor failure
Solutions:Replace PBA
E470EEPROM data error (no data)
Causes:Corrupted outdoor PCB
Solutions:Replace outdoor PCB
E483Over-voltage protection
Causes:Voltage spike
Solutions:Check power supply
E500Heatsink over-temperature
Causes:Blocked airflow around heatsink
Solutions:Clean heatsink; Check ventilation
E504Compressor self-diagnosis error
Causes:Compressor fault
Solutions:Professional service required

Outdoor Fan

CodeDescription
E446Fan 1 operation failure
Causes:Motor failure
Solutions:Replace fan motor
E447Fan 1 wire not connected
Causes:Loose wiring
Solutions:Reconnect fan wiring
E448Fan 1 lock error
Causes:Obstruction; Motor seizure
Solutions:Clear obstruction; Replace motor
E452ZPC / instant power failure
Causes:Power interruption
Solutions:Check power stability
E453Fan 1 overheated
Causes:High load; Bearing failure
Solutions:Allow cooling; Replace motor
E458Outdoor fan error (general)
Causes:Motor failure
Solutions:Replace fan motor
E915DC fan non-operating
Causes:DC fan failure
Solutions:Replace DC fan

Refrigerant/Pressure

CodeDescription
E401Freezing detection 1
Causes:Low refrigerant; Poor airflow; Blocked coil
Solutions:Check refrigerant charge; Clean coil
E402Freezing detection 2
Causes:Low refrigerant; Poor airflow; Blocked coil
Solutions:Check refrigerant charge; Clean coil
E403Freezing detection 3
Causes:Low refrigerant; Poor airflow; Blocked coil
Solutions:Check refrigerant charge; Clean coil
E407High pressure protection 1
Causes:Blocked condenser; Overcharge; Fan failure
Solutions:Check airflow; Check refrigerant charge
E408High pressure protection 2
Causes:Blocked condenser; Overcharge; Fan failure
Solutions:Check airflow; Check refrigerant charge
E409High pressure protection 3
Causes:Blocked condenser; Overcharge; Fan failure
Solutions:Check airflow; Check refrigerant charge
E410Low pressure protection 1
Causes:Refrigerant leak; Blocked filter drier
Solutions:Check for leaks; Inspect filter drier
E411Low pressure protection 2
Causes:Refrigerant leak; Blocked filter drier
Solutions:Check for leaks; Inspect filter drier
E412Low pressure protection 3
Causes:Refrigerant leak; Blocked filter drier
Solutions:Check for leaks; Inspect filter drier
E413Sump down protection 1
Causes:Liquid refrigerant in compressor sump
Solutions:Check EEV; Check superheat
E414Sump down protection 2
Causes:Liquid refrigerant in compressor sump
Solutions:Check EEV; Check superheat
E415Sump down protection 3
Causes:Liquid refrigerant in compressor sump
Solutions:Check EEV; Check superheat
E416Discharge temp protection 1
Causes:Low refrigerant; High compression ratio
Solutions:Check refrigerant charge
E417Discharge temp protection 2
Causes:Low refrigerant; High compression ratio
Solutions:Check refrigerant charge
E418Discharge temp protection 3
Causes:Low refrigerant; High compression ratio
Solutions:Check refrigerant charge
E419EEV self-diagnosis error 1
Causes:EEV mechanical or electrical failure
Solutions:Check EEV; Replace EEV
E420EEV self-diagnosis error 2
Causes:EEV mechanical or electrical failure
Solutions:Check EEV; Replace EEV
E421EEV self-diagnosis error 3
Causes:EEV mechanical or electrical failure
Solutions:Check EEV; Replace EEV
E422EEV self-diagnosis error 4
Causes:EEV mechanical or electrical failure
Solutions:Check EEV; Replace EEV
E423EEV self-diagnosis error 5
Causes:EEV mechanical or electrical failure
Solutions:Check EEV; Replace EEV
E424EEV self-diagnosis error 6
Causes:EEV mechanical or electrical failure
Solutions:Check EEV; Replace EEV
E425Reverse phase detection 1
Causes:3-phase wiring error
Solutions:Swap two phase wires
E426Reverse phase detection 2
Causes:3-phase wiring error
Solutions:Swap two phase wires
E427Reverse phase detection 3
Causes:3-phase wiring error
Solutions:Swap two phase wires
E428Compression ratio error 1
Causes:Abnormal pressure differential
Solutions:Check circuit; Check valves
E429Compression ratio error 2
Causes:Abnormal pressure differential
Solutions:Check circuit; Check valves
E430Compression ratio error 3
Causes:Abnormal pressure differential
Solutions:Check circuit; Check valves
E439Refrigerant leakage detected
Causes:Refrigerant leak
Solutions:Leak test; Repair leak; Recharge system
E442Charging error in heating mode
Causes:Incorrect refrigerant charge
Solutions:Correct refrigerant charge
E503Service valve closed
Causes:Valve left shut after maintenance
Solutions:Open service valve
E554Full refrigerant leak detected
Causes:Major outdoor unit leak
Solutions:Emergency — professional repair required immediately

Water/Hydro

CodeDescription
E901Water inlet pipe sensor (short/open)
Causes:Sensor failure
Solutions:Replace sensor
E902Water outlet pipe sensor (short/open)
Causes:Sensor failure
Solutions:Replace sensor
E904Water tank sensor (short/open)
Causes:Sensor failure
Solutions:Replace sensor
E907Pipe rupture protection
Causes:Abnormal pressure or flow detected
Solutions:Check piping for damage
E908Freeze prevention (recoverable)
Causes:Freezing risk detected
Solutions:Check antifreeze concentration; Check insulation
E909Freeze prevention (non-recoverable)
Causes:Critical freeze event
Solutions:Professional service required
E910Water outlet sensor detached
Causes:Sensor not in pocket
Solutions:Reinsert sensor into pocket
E911Flow switch ON / pump OFF / low flow
Causes:Flow switch malfunction; Low flow rate; Zone valve not opening; Clogged filter; Air in system
Solutions:Replace flow switch; Clean filter; Bleed air from system; Check valves are opening; Add bypass valve; Check pump speed
E912Flow detected with no demand
Causes:Stuck relay or valve; Faulty PCB; Thermosiphon effect
Solutions:Check valves; Inspect relay and PCB; Add non-return valve
E913Six flow switch errors (lockout)
Causes:Repeated E911/E912 errors
Solutions:Resolve underlying flow issue; Reset unit
E914Incorrect thermostat connection
Causes:Wired incorrectly
Solutions:Rewire per installation manual
E917Water tank sensor config error
Causes:Misconfigured or absent sensor
Solutions:Configure sensor correctly
E919Legionella disinfection incomplete
Causes:Cylinder didn't reach 60°C in 8 hours; Runs at 3am Tuesday by default
Solutions:Check immersion heater is working; Verify sensor position (100mm into tank, above immersion element); Set thermostat above 60°C; Disable if mains-fed unvented tank

Display/Informational

CodeDescription
ChCompressor starting delay / crankcase heater
Causes:Normal startup sequence
Solutions:No action needed — normal operation
CFFilter cleaning reminder
Causes:Scheduled maintenance reminder
Solutions:Clean the filter
CIAuto clean function
Causes:Normal auto-clean cycle
Solutions:No action needed — normal operation
dFDefrost in progress
Causes:Ice build-up on outdoor coil
Solutions:No action needed — normal defrost cycle
E551Defrosting operation
Causes:Active defrost cycle
Solutions:No action needed — normal operation
E553Equability operation
Causes:System balancing in progress
Solutions:No action needed — system balancing