Settings & Configuration Guide

A practical guide to getting the most from your Samsung EHS heat pump. This covers the why and how of key settings — not just what they do, but how to set them up for comfort and efficiency.

Every 1°C reduction in flow temperature improves COP by ~2–3%

Lower flow temperatures are the single biggest lever for heat pump efficiency. The settings below help you achieve the lowest comfortable flow temperature.

Weather Compensation (Water Law)

What is it?

Samsung calls weather compensation “Water Law”. It automatically adjusts your flow temperature based on outdoor air temperature — sending hotter water to your emitters when it’s cold outside, and cooler water when it’s mild. This is controlled by FSV settings 201* to 203*.

The curve is defined by two points: a cold outdoor temperature paired with a high flow temperature, and a warm outdoor temperature paired with a low flow temperature. The system interpolates linearly between them.

Practical Setup Method

  1. Find your cold-day comfort point. On a cold day (0–5°C outside), note the flow temperature that keeps your home comfortable. This is your high target value.
  2. Find your mild-day comfort point. On a mild day (~15°C outside), note the lowest flow temperature that still provides adequate warmth. This is your low target value.
  3. Set the curve. Enter these two points into the water law settings (FSV 2021/2022 for WL1 or 2031/2032 for WL2). Set the outdoor temperatures (FSV 2011/2012) to match when you took the readings.
  4. Fine-tune over a week or two. Adjust by 1–2°C at a time. A typical heating curve has a slope of 0.6–0.8 with an offset of +2 to +3.

Example Weather Compensation Curves

The chart below shows typical water law curves for underfloor heating (UFH) and radiators. As outdoor temperature rises, the target flow temperature drops — saving energy in mild weather.

-15°-10°-5°0°5°10°15°20°20°25°30°35°40°45°50°55°Outdoor Temperature (°C)Flow Temperature (°C)50°C35°C40°C25°CUFH (WL1)Radiators (WL2)
UFH (WL1)

At −10°C outdoor → 40°C flow

At 15°C outdoor → 25°C flow

Radiators (WL2)

At −10°C outdoor → 50°C flow

At 15°C outdoor → 35°C flow

Common Mistake: Reversed High/Low Values

Many installers accidentally reverse the water law values — setting the high flow temperature against the warm outdoor temperature and vice versa. The result: lukewarm radiators in cold weather and unnecessarily hot water on mild days. If your system feels backwards, check that the high flow temp is paired with the cold outdoor temp (Point ②), and the low flow temp with the warm outdoor temp (Point ①).

Default Minimum Flow Temperature

The default Samsung water law curve has a minimum flow temperature of 37°C. This ensures radiators always feel warm to the touch, even in mild conditions. While this prevents complaints about “cold radiators”, it can reduce efficiency. If your home is well-insulated and you’re comfortable with radiators that are merely warm (not hot) in mild weather, you can lower the minimum to 25–30°C for better COP.

Key FSV Settings

Accessing Service Mode: Hold the up + down arrows on the wired controller for 10 seconds, then enter password 0202. For the complete FSV reference, see the FSV Reference Guide.

FSVNameRecommendedWhy
#2091External Thermostat #1Setting 4Best pump cycling balance — prevents unwanted anti-frost cycles
#2092External Thermostat #2Setting 4Same as above for second zone (FCU/radiator)
#201*–203*Water Law SettingsMatch to heat lossEnsures correct flow temps for your emitters and climate
#3023HP ON temp diff10°C+Fewer, longer DHW cycles are more efficient
#3025Max DHW operation time95 minGives the HP time to finish DHW before immersion fires
#3032Booster delay time60–90 minLet the heat pump work before expensive immersion kicks in
#3041Samsung disinfectionNot Use (0)Runs too often, wastes energy — use a weekly timer instead
#3021Max HP temp for DHW55°C (R32)Maximum the heat pump can achieve with R32 refrigerant
#3022HP OFF temp diff0°CHeat pump stops at the set temperature, no overshoot
#3083BSH energy meteringActual kW ratingEnsures accurate energy monitoring on the controller display

FSV 2091/2092: Pump Mode

FSV #2091 and #2092 control how the water pump behaves when using a third-party thermostat (external room thermostat). The setting determines what happens during “thermo-off” periods — when the thermostat is satisfied and the compressor stops.

Setting 2: Pump off when compressor off

Saves pump energy, but radiators cool down faster. Water stops circulating immediately when the compressor stops.

Setting 3: Pump runs while thermostat active

More even heat distribution — water keeps circulating even when the compressor cycles off, as long as the thermostat is calling for heat. Uses more pump energy.

Setting 4: 7 min off / 3 min on cycling (Recommended)

The best balance for most installations. During thermo-off, the pump cycles with 7 minutes off and 3 minutes on. This prevents the system from triggering unwanted anti-frost (AF) protection cycles — which can extract heat from your DHW tank and waste energy — while still saving pump energy compared to Setting 3.

Note: These settings only apply when using external room thermostats. If you’re using the Samsung wired controller for room temperature control, leave #2091 and #2092 at 0.

DHW Optimization

Disable Samsung Disinfection

Set FSV #3041 to Not Use (0). Samsung’s built-in legionella disinfection cycle runs too frequently and uses the immersion heater to heat the tank to 70°C — wasting significant energy.

Instead, use your immersion heater on a weekly timer (e.g., Tuesday 3am) with the thermostat set to 60°C or above. This gives the same legionella protection at a fraction of the energy cost. For vulnerable occupants, target 65°C.

Reduce DHW Cycling

Increase FSV #3023 (HP ON temp diff) to 10°C or higher. The default of 5°C causes the heat pump to start a DHW cycle whenever the tank drops just 5°C below the off point — leading to frequent, short, inefficient cycles. A larger hysteresis means fewer, longer cycles with better COP.

Give the Heat Pump Time

Increase FSV #3032 (booster delay) to 60–90 minutes. The default 20-minute delay is too short — the immersion heater fires before the heat pump has had a chance to finish heating DHW. The immersion uses roughly 3x the energy per kWh of heat delivered compared to the heat pump.

Tip: Ensure the booster delay (#3032) is shorter than the max DHW operation time (#3025). Setting #3025 to 95 minutes gives the heat pump maximum working time.

Tank Sensor Placement

The DHW tank temperature sensor must be fully inserted into the middle pocket of the cylinder and secured in place. A sensor that has slipped out or is poorly positioned will give inaccurate readings — causing the heat pump to over- or under-heat the tank, and potentially triggering E919 legionella failure errors.

Quiet Mode

Quiet mode reduces compressor and fan speed on the outdoor unit to lower noise levels. There are 4 levels (0–3), with level 3 being the quietest — reducing noise by up to 30% (down to 35 dBA on HT Quiet models).

How to Configure

Quiet mode is configured via the outdoor unit LED display, not the indoor control panel. Set the four display segments to:

0 / 3 / 0 / x

where x = quiet level (0–3)

When to Use

  • Good for: Nighttime noise reduction (10pm–8am), DHW heating in mild weather, any time neighbours are noise-sensitive
  • Best for: Level 1–2 as a permanent setting in noise-sensitive locations

Avoid Quiet Mode for Space Heating Below ~10°C

At lower outdoor temperatures the heat pump needs to work harder. Restricting its output with quiet mode in cold weather can paradoxically increase both noise and energy consumption — the compressor runs longer at suboptimal efficiency trying to meet demand. Quiet mode is most effective in mild conditions where the unit has spare capacity.

Defrost vs Frost Prevention

These are two different processes that are often confused. Both involve the outdoor unit, but they serve different purposes and behave very differently.

Real Defrost

  • Triggers when evaporator outlet temperature reaches ≤ -6°C
  • Reverses the refrigerant cycle (hot gas) to melt ice on the outdoor coil
  • Takes 5–15 minutes, occurs roughly every 70 minutes at -5.5°C ambient
  • Normal and expected — you’ll see steam from the outdoor unit
  • Display shows dF during defrost

Frost Prevention (Anti-Frost)

  • Triggers when ambient is <3–5°C and the system has been idle for 60+ minutes
  • Runs the circulation pump for ~5 minutes to prevent pipework freezing
  • Problem: Extracts heat from the DHW tank, causing ~8°C drops overnight
  • Cannot be disabled — it is fixed Samsung protection logic
  • FSV 2091/2092 Setting 4 helps reduce the impact by managing pump cycling

Tip: If your DHW tank temperature drops significantly overnight in cold weather despite no hot water usage, frost prevention is the likely cause. Using FSV 2091/2092 Setting 4 (the 7/3 pump cycling) helps minimise the heat extracted from the tank during these protection cycles.

Flow Temperature by Emitter Type

The table below gives recommended flow temperatures for common emitter types. Lower flow temperatures mean higher COP — so always aim for the lowest temperature that maintains comfort.

Emitter TypeDesign Flow TempWeather Comp RangeNotes
Underfloor Heating35–40°C25–40°CNever exceed 45°C
Oversized Radiators35–45°C30–45°CBest for COP
Standard Radiators45–55°C35–55°CSet max to your design temp
Fan Coil Units35–45°C30–45°CFan compensates for lower temps

Need the complete FSV reference?

This guide covers the most impactful settings. For every FSV code with defaults, ranges, and detailed notes, see the full reference.

View FSV Reference Guide

Important notes

  • This guide is based on Samsung EHS Gen 6 (R32) systems. Some settings may differ on Gen 5, Gen 7 (R290), or ClimateHub models.
  • FSV changes should only be made by a qualified installer who understands the implications for your specific system.
  • Always note down your current FSV values before making changes so you can revert if needed.